home

Leaders in the Design and Manufacture of Custom-Built Cable Bus Systems

 

600V, 5kV, 15kV, & 35kV Cable Bus Ratings Using Copper Cable

 

Amperage Rating

Voltage Class

Cable Size

Cables Per Phase

Cable Configuration

Overall Housing

 

 

 

 

Rows x Cables

  Size (inches)

 

 

 

 

 

 

1200A

600V

500MCM

2

2 x 3

8.13 x 17.50

 

5000V

 500MCM

2

2 x 3

8.13 x 17.50

 

15000V

 500MCM

2

2 x 3

8.13 x 17.50

 

35000V

 500MCM

2

2 x 3

10.13  x 19.50

 

 

 

 

 

 

1600A

600V

750MCM

2

2 x 3

8.13 x 17.50

 

5000V

 750MCM

2

2 x 3

10.13  x 19.50

 

15000V

 750MCM

2

2 x 3

10.13  x 19.50

 

35000V

 750MCM

2

2 x 3

10.13  x 19.50

 

 

 

 

 

 

2000A

600V

750MCM

3

2 x 5

8.13 x 23.50

 

5000V

750MCM

3

2 x 5

8.13 x 23.50

 

15000V

750MCM

3

2 x 5

8.13 x 25.50

 

35000V

750MCM

3

2 x 5

10.13 x 25.50

 

 

 

 

 

 

2500A

600V

500MCM

4

2 x 6

8.13 x 26.50

 

5000V

500MCM

4

2 x 6

8.13 x 26.50

 

15000V

500MCM

4

2 x 6

10.13 x 26.50

 

35000V

500MCM

4

2 x 6

10.13 x 29.50

 

 

 

 

 

 

3000A

600V

750MCM

4

2 x 6

8.13 x 26.50

 

5000V

750MCM

4

2 x 6

8.13 x 26.50

 

15000V

750MCM

4

2 x 6

10.13 x 29.50

 

35000V

750MCM

4

2 x 6

 12.13 x 31.50

 

 

 

 

 

 

3500A

600V

1000MCM

4

2 x 6

8.13 x 26.50

 

5000V

1000MCM

4

2 x 6

10.13 x 29.50

 

15000V

1000MCM

4

2 x 6

10.13 x 29.50

 

35000V

1000MCM

4

2 x 6

 12.13 x 31.50

 

 

 

 

 

 

4000A

600V

750MCM

6

3 x 6

10.13 x 26.50

 

5000V

750MCM

6

3 x 6

12.13 x 29.50

 

15000V

750MCM

6

3 x 6

14.13 x 31.50

 

35000V

750MCM

6

3 x 6

 16.13  x 35.50

 

 

 

 

 

 

5000A

600V

1000MCM

6

3 x 6

12.13 x 29.50

 

5000V

1000MCM

6

3 x 6

12.13 x 29.50

 

15000V

1000MCM

6

3 x 6

14.13 x 35.50

 

35000V

1000MCM

6

3 x 6

16.13 x 35.50